Energy savings: _____ KWh per year
Money saved : _____ per year






| 800*600*2200 | 30K~100K, 4 units in max (Ultra) |
| 1000*600*2200 | 30K~100K, 5 units in max (Ultra) |
| 1200*600*2200 | 30K~100K, 6 units in max (Ultra) |




| Performance indicators | ||||
| Rating | 50K | 60K | 100K | 200K |
| Control Algorithm | FFT, intelligent FFT, and instantaneous reactive power | |||
| Fast Response Time | < 50us | |||
| Full Response Time | < 15ms | |||
| Target Power Factor | Adjustable from -1 to +1 | |||
| Switching frequency | Average 40kHz,up to 95kHz | |||
| Cooling Air Requirement | 180CFM | 240CFM | 480CFM | |
| Noise Level | <60dB (Full load) | <65dB (Full load) | <68dB (Full load) | |
| Communications Ports | RS485 and Ethernet port(RJ45) | |||
| Communications Protocols | Modbus RTU, TCP/IP | |||
| Module Display Interface | 4.3-inch HMI(module), 7-inch HMI(central monitor) and LED | |||
| Protection Functions | Over-voltage protection, under-voltage protection, inverter bridge inverse protection, over-compensation protection and so on | |||
| Mounting Type | Wall-mounted, Rack-mounted and Cabinet | Wall-mounted and Rack-mounted | ||
| Dimensions (W*D*H mm) | 500*470*88 | 500*520*88 | 500*520*100 | 500*646*220 |
| Net Weight | 24kg | 27kg | 31kg | 63kg |
| Storage Temperature | -40℃~70℃ | |||
| Operating Ambient Temperature | -10℃~40℃ (may derate capacity if ambient temperature exceeds 40℃) | |||
| Relative Humidity | 5% to 95%, non-condensing | |||
| Altitude | ≤1500m, 1500-4000m, capacity is derating 1% for every 100m altitude increased. | |||
| Relative | IP20 (IP degree can be customizable) | |||